MEAN WELL true sine wave inverters, battery chargers and DC-DC converters for the battery side of off-grid cabins, RVs and backup systems. Note: our MEAN WELL catalog does not include MPPT solar charge controllers, so pair these with the charge controller of your choice.
Solar panels charge the battery through a charge controller. The battery then feeds an inverter for 120VAC loads and DC-DC converters for 12V or 24V loads. A battery charger tops the bank up from the grid or a generator.
True sine wave inverters (TS, NTS, NTU, TN) run AC loads from a 12V, 24V or 48V battery.
NPB, PB, ENC and DBR chargers with lead-acid and lithium charge curves.
SD, RSD, DDR and DDRH convert the battery voltage to the 12V or 24V your loads need.
True sine wave output for electronics, pumps, compressors and chargers. In TS and TN model numbers the digit after the wattage gives the AC output (1 = 100–120VAC, 2 = 200–240VAC) and the last two digits the battery voltage (12, 24 or 48 V). Check the datasheet for surge power and outlet type.
The NTS-1700-148US runs from a 48V battery (40–66 V input) and delivers 1700 W continuous with 3000 W surge (30 cycles) per its datasheet. NTU models add a UPS (transfer) function, and NTN and ISI models cover other power levels and battery voltages; check each datasheet.
A lower-cost option for simple resistive loads. For electronics, motors and chargers use a pure sine wave model above.
The NPB series datasheet lists a 2-stage charging curve for Li-ion batteries (lithium iron and lithium manganese) and a 3-stage curve for lead-acid (flooded, gel and AGM), selectable by DIP switch. Set the curve to match your battery and BMS.
Also listed: NPP, PB, RPB, RCB, DBR, DBU, NCP, ENC, ENP, ESC, ESP, PA and HEP charger models. Charging curves and battery types differ by series; check the datasheet.
Run DC loads straight from the battery without an inverter. DDR-240C-24 takes a 48V bank (33.6–67.2 V input) down to 24V, DDR-120A-24 steps a 12V bank (9–18 V input) up to 24V, and SD-350B-24 gives an isolated, regulated 24V from a 24V bank (20–36 VDC input). DDRH and RSDH are designed for PV / renewable energy systems.
Add up the running watts of everything that can be on at the same time and divide by 0.8. Then check the start-up surge of motors and compressors (often several times their running watts) against the inverter surge rating.
Battery current is roughly inverter watts ÷ battery voltage ÷ efficiency, so a 1700 W load on a 48V bank draws about 37.5 A, while the same load on 12V would need over 140 A.
For systems that both charge and discharge a battery through one unit, the BIC series is a bidirectional AC⇄DC power supply, and the NTN-5K series is a 5 kW true sine wave inverter with AC charger and UPS function (per its datasheet). Both are quoted per project: tell us the battery voltage, power and grid conditions.
List the loads that can run at the same time, add their running watts and divide by 0.8 for the continuous rating. Then make sure the surge rating covers the start-up of the largest motor or compressor. Above about 1–2 kW, a 24V or 48V battery bank keeps the current manageable.
Pure (true) sine wave inverters work with electronics, motors, compressors and chargers. Modified sine wave is cheaper but can cause noise, heat or malfunction in some motors and electronics. For mixed loads, choose true sine wave.
Yes, with a model whose datasheet lists a lithium curve. The NPB series offers a 2-stage curve for Li-ion (lithium iron and lithium manganese) batteries; set it to match the battery and BMS limits.
Higher voltage means lower current for the same power, so thinner cables and lower losses. 12V suits small RV and cabin systems, 24V mid-size systems, and 48V systems of a few kilowatts.
No. These inverters run from a battery. Solar panels must charge the battery through a charge controller, which is not part of our MEAN WELL catalog.
The NTU series is a true sine wave inverter with UPS function: it passes utility AC to the load and switches to battery power when the utility fails. Ask us for the transfer details of the model you need.
Use a DC-DC converter with a 48V-range input and 12V output from the SD, RSD or DDR series, sized at the 12V load ÷ 0.8. This avoids running small DC loads through the inverter.
Send your battery voltage, the loads you want to run and the backup time to sales@htdelectronics.com, or request a quote.